Table 18: SG operation mode = “Logic mode 2”
Input
BI_SG_2 BI_SG_3 BI_SG_4 BI_SG_5 BI_SG_6 Active group
FALSE FALSE FALSE any any 1
TRUE FALSE FALSE any any 2
any TRUE FALSE any any 3
any any TRUE FALSE FALSE 4
any any TRUE TRUE FALSE 5
any any TRUE any TRUE 6
The setting group 1 can be copied to any other or all groups from HMI (Copy group
1).
3.6 Test mode
3.6.1 Function blocks
GUID-DFF8F71A-895C-4C06-B287-63C3CA26154C V2 EN
GUID-FA386432-3AEF-468D-B25E-D1C5BDA838E3 V3 EN
Figure 23: Function blocks
3.6.2 Functionality
The mode of all the logical nodes in the relay's IEC 61850 data model can be set with
Test mode. Test mode is selected through one common parameter via the WHMI path
Tests/IED test. By default, Test mode can only be set locally through LHMI. Test
mode is also available via IEC 61850 communication (LD0.LLN0.Mod).
Section 3 1MRS758755 A
Basic functions
62 REC615 and RER615
Technical Manual