remote and local status indication of, for example, disconnectors, air-break switches
and earthing switches, which represent the lowest level of power switching devices
without short-circuit breaking capability.
9.2.6 Signals
Table 642: DCSXSWI Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE BOOLEAN 0=False
Signal for close position of apparatus from I/O
1)
1) Not available for monitoring
Table 643: ESSXSWI Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE BOOLEAN 0=False
Signal for close position of apparatus from I/O
1)
1) Not available for monitoring
Table 644: DCSXSWI Output signals
Name
Type Description
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
Table 645: ESSXSWI Output signals
Name
Type Description
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
9.2.7 Settings
Table 646: DCSXSWI Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Identification DCSXSWI1 switch
position
Control Object identification
1MRS758755 A Section 9
Control functions
REC615 and RER615 615
Technical Manual