4.6 Power protection
4.6.1 Three-phase power directional element DPSRDIR
4.6.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase power directional element DPSRDIR I1-> 32P
4.6.1.2 Function block
RELEAS E
I1
DPSRDIR
U1
BLOCK
GUID-789C0387-72AC-49D3-855D-3BC499251C8B V1 EN
Figure 229: Function block
4.6.1.3 Functionality
The three-phase power directional element DPSRDIR is used to detect positive-
sequence power direction. The output of the function is used for blocking or releasing
other functions in protection scheme.
The directional positive-sequence power protection contains a blocking functionality
which blocks function output and resets Timer.
4.6.1.4 Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of DPSRDIR can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
1MRS758755 A Section 4
Protection functions
REC615 and RER615 453
Technical Manual