When the station authority level “L,S,R” is used, the control access can be selected
using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input CTRL_STA are applicable
for this station authority level.
Station control access can be reserved by using R/L button or CONTROL function
block together with IEC 61850 data object CTRL.LLN0.LocSta.
Table 168: Station authority level “L,S,R” using R/L button
L/R Control L/R Control status Control access
R/L button
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
Local FALSE FALSE 1 x
Remote FALSE FALSE 2 x
Remote TRUE FALSE 3 x
Off FALSE FALSE 0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
Table 169: Station authority level “L,S,R” using CONTROL function block
L/R Control
L/R Control status Control access
Control FB input
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
CTRL_OFF FALSE FALSE 0
CTRL_LOC FALSE FALSE 1 x
CTRL_STA TRUE FALSE 3 x
CTRL_REM
4)
TRUE FALSE 3 x
CTRL_REM FALSE FALSE 2 x
CTRL_ALL FALSE FALSE 0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.16.11.7 Station authority level “L,S,S+R,L+S,L+S+R”
Station authority level “L,S,S+R,L+S,L+S+R” adds station control access together
with several different multilevel access scenarios. Control access can also be
simultaneously permitted from local, station or remote location. Simultaneous local,
station or remote control operation is not allowed as one client and location at time can
access controllable objects and they remain reserved until the previously started
control operation is first completed by the client.