9.4.4.2 Shot initiation
A070869 V1 EN
Figure 332: Example of an autoreclosing program with a reclose scheme matrix
In the AR function, each shot can be programmed to locate anywhere in the reclose
scheme matrix. The shots are like building blocks used to design the reclose program.
The building blocks are called CBBs. All blocks are alike and have settings which give
the attempt number (columns in the matrix), the initiation or blocking signals (rows in
the matrix) and the reclose time of the shot.
The settings related to CBB configuration are:
First...Seventh reclose time
Init signals CBB1…CBB7
Blk signals CBB1…CBB7
Shot number CBB1…CBB7
The reclose time defines the open and dead times, that is, the time between the
OPEN_CB and the CLOSE_CB commands. The Init signals CBBx setting defines the
initiation signals. The Blk signals CBBx setting defines the blocking signals that are
related to the CBB (rows in the matrix). The Shot number CBB1…CBB7 setting
defines which shot is related to the CBB (columns in the matrix). For example, CBB1
settings are:
Section 9 1MRS758755 A
Control functions
638 REC615 and RER615
Technical Manual