3.6.8 Signals
Table 22: PROTECTION input signals
Name
Type Default Description
BI_SG_2 BOOLEAN 0 Setting group 2 is
active
BI_SG_3 BOOLEAN 0 Setting group 3 is
active
BI_SG_4 BOOLEAN 0 Setting group 4 is
active
BI_SG_5 BOOLEAN 0 Setting group 5 is
active
BI_SG_6 BOOLEAN 0 Setting group 6 is
active
Table 23: CONTROL input signals
Name Type Default Description
CTRL_OFF BOOLEAN 0 Control OFF
CTRL_LOC BOOLEAN 0 Control local
CTRL_STA BOOLEAN 0 Control station
CTRL_REM BOOLEAN 0 Control remote
CTRL_ALL BOOLEAN 0 Control all
Table 24: PROTECTION output signals
Name
Type Description
SG_LOGIC_SEL BOOLEAN Logic selection for setting group
SG_1_ACT BOOLEAN Setting group 1 is active
SG_2_ACT BOOLEAN Setting group 2 is active
SG_3_ACT BOOLEAN Setting group 3 is active
SG_4_ACT BOOLEAN Setting group 4 is active
SG_5_ACT BOOLEAN Setting group 5 is active
SG_6_ACT BOOLEAN Setting group 6 is active
BEH_BLK BOOLEAN Logical device LD0 block status
BEH_TST BOOLEAN Logical device LD0 test status
FRQ_ADP_FAIL BOOLEAN Frequency adaptivity status fail
Table 25: CONTROL output signals
Name
Type Description
OFF BOOLEAN Control OFF
LOCAL BOOLEAN Control local
STATION BOOLEAN Control station
Table continues on next page