8.1.11.5 Monitored data
Table 613: PEMMXU Monitored data
Name
Type Values (Range) Unit Description
S-kVA FLOAT32 -999999.9...9999
99.9
kVA Total Apparent Power
P-kW FLOAT32 -999999.9...9999
99.9
kW Total Active Power
Q-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Total Reactive Power
PF FLOAT32 -1.00...1.00 Average Power factor
RSTACM BOOLEAN 0=False
1=True
Reset of accumulated
energy reading
S_INST FLOAT32 -999999.9...9999
99.9
kVA Apparent power,
magnitude of
instantaneous value
S_DB
FLOAT32 -999999.9...9999
99.9
kVA Apparent power,
magnitude of reported
value
S_DMD
FLOAT32 -999999.9...9999
99.9
kVA Demand value of
apparent power
P_INST FLOAT32 -999999.9...9999
99.9
kW Active power, magnitude
of instantaneous value
P_DB FLOAT32 -999999.9...9999
99.9
kW Active power, magnitude
of reported value
P_DMD FLOAT32 -999999.9...9999
99.9
kW Demand value of active
power
Q_INST FLOAT32 -999999.9...9999
99.9
kVAr Reactive power,
magnitude of
instantaneous value
Q_DB
FLOAT32 -999999.9...9999
99.9
kVAr Reactive power,
magnitude of reported
value
Q_DMD
FLOAT32 -999999.9...9999
99.9
kVAr Demand value of reactive
power
PF_INST FLOAT32 -1.00...1.00 Power factor, magnitude
of instantaneous value
PF_DB FLOAT32 -1.00...1.00 Power factor, magnitude
of reported value
PF_DMD FLOAT32 -1.00...1.00 Demand value of power
factor
EA_RV_ACM INT64 0...999999999 kWh Accumulated reverse
active energy value
ER_RV_ACM INT64 0...999999999 kVArh Accumulated reverse
reactive energy value
EA_FWD_ACM INT64 0...999999999 kWh Accumulated forward
active energy value
ER_FWD_ACM INT64 0...999999999 kVArh Accumulated forward
reactive energy value
Table continues on next page
1MRS758755 A Section 8
Measurement functions
REC615 and RER615 583
Technical Manual