ABB RELION Series - Function Block; Three-Phase Directional Overcurrent Protection (F)Dphxpdoc223 Identification

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 235: PHHPTOC Technical revision history
Technical revision Change
C
Measurement mode
"P-to-P + backup" replaced
with "Peak-to-Peak"
D Step value changed from 0.05 to 0.01 for the
Time
multiplier
setting
E Internal improvement
F Internal improvement
Table 236: (F)PHLPTOC Technical revision history
Technical revision Change
B Minimum and default values changed to 40 ms for
the
Operate delay time
setting
C Step value changed from 0.05 to 0.01 for the
Time
multiplier
setting
D Internal improvement
E Internal improvement
4.1.2 Three-phase directional overcurrent protection
(F)DPHxPDOC
4.1.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase directional overcurrent
protection, low stage
(F)DPHLPDOC 3I> -> 67-1
Three-phase directional overcurrent
protection, high stage
DPHHPDOC 3I>> -> 67-2
4.1.2.2 Function block
FDPHLPDOC
I_B
I_A
START
OPERATE
I
2
I_C
U_B_BC
U_A_AB
U
1
U_C_CA
U
2
BLOCK
ENA_MULT
NON_DIR
DPHHPDOC
I_B
I_A
START
OPERATE
I
2
I_C
U_B_BC
U_A_AB
U
1
U_C_CA
U
2
BLOCK
ENA_MULT
NON_DIR
GUID-24B6C85F-8A9F-4A06-A449-848954A2697E V1 EN
Figure 120: Function block
1MRS758755 A Section 4
Protection functions
REC615 and RER615 223
Technical Manual