Each control point or SPCRGAPC can only be accessed remotely through
communication. SPCRGAPC follows the local or remote (L/R) state if the setting Loc
Rem restriction is "true". If the Loc Rem restriction setting is "false", local or remote
(L/R) state is ignored, that is, all controls are allowed regardless of the local or remote
state.
The BLOCK input can be used for blocking the output functionality. The BLOCK input
operation depends on the Operation mode setting. If the Operation mode setting is set
to "Toggle", the output state cannot be changed when the input BLOCK is TRUE. If the
Operation mode setting is set to "Pulsed", the activation of the BLOCK input resets the
output to the FALSE state.
3.16.13.4 Signals
Table 179: SPCRGAPC Input signals
Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
Table 180: SPCRGAPC Output signals
Name
Type Description
O1 BOOLEAN Output 1 status
O2 BOOLEAN Output 2 status
O3 BOOLEAN Output 3 status
O4 BOOLEAN Output 4 status
O5 BOOLEAN Output 5 status
O6 BOOLEAN Output 6 status
O7 BOOLEAN Output 7 status
O8 BOOLEAN Output 8 status
O9 BOOLEAN Output 9 status
O10 BOOLEAN Output 10 status
O11 BOOLEAN Output 11 status
O12 BOOLEAN Output 12 status
O13 BOOLEAN Output 13 status
O14 BOOLEAN Output 14 status
O15 BOOLEAN Output 15 status
O16 BOOLEAN Output 16 status