Table 647: DCSXSWI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 30000 Event delay of the intermediate position
Vendor 0 External equipment vendor
Serial number 0 External equipment serial number
Model 0 External equipment model
Table 648: ESSXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Identification ESSXSWI1 switch
position
Control Object identification
Table 649: ESSXSWI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 30000 Event delay of the intermediate position
Vendor 0 External equipment vendor
Serial number 0 External equipment serial number
Model 0 External equipment model
9.2.8 Monitored data
Table 650: DCSXSWI Monitored data
Name
Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position
indication
Table 651: ESSXSWI Monitored data
Name
Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position
indication
Section 9 1MRS758755 A