Table 389: MFADPSDE Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Operation mode 1=Intermittent EF
3=General EF
4=Alarming EF
3=General EF Operation criteria
Table 390: MFADPSDE Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used Io signal
Uo signal Sel 1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used Uo signal
Peak counter limit 2...20 1 2 Peak counter limit for restriking EF
Start delay time 30...60000 ms 1 30 Start delay time
Reset delay time 0...60000 ms 1 500 Reset delay time
Pol reversal 0=False
1=True
0=False Rotate polarizing quantity
4.2.7.8 Monitored data
Table 391: MFADPSDE Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE FLOAT32 -180.00...180.00 deg Angle between polarizing
and operating quantity
MFADPSDE Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status