3.18 Load profile record LDPRLRC
3.18.1 Function block
GUID-FE70FC2E-8582-4450-97F1-B9D699809951 V1 EN
Figure 109: Function block
3.18.2 Functionality
The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand interval).
Up to 12 load quantities can be selected for recording and storing in a nonvolatile
memory. The value range for the recorded load quantities is about eight times the
nominal value, and values larger than that saturate. The recording time depends on a
settable demand interval parameter and the amount of quantities selected. The record
output is in the COMTRADE format.
3.18.2.1 Quantities
Selectable quantities are product-dependent.
Table 192: Quantity Description
Disabled
Quantity not selected
IL1 Phase 1 current
IL2 Phase 2 current
IL3 Phase 3 current
Io Neutral/earth/residual current
U12 Phase-to-phase 12 voltage
U23 Phase-to-phase 23 voltage
U31 Phase-to-phase 31 voltage
UL1 Phase-to-earth 1 voltage
UL2 Phase-to-earth 2 voltage
UL3 Phase-to-earth 3 voltage
U12B Phase-to-phase 12 voltage, B side
U23B Phase-to-phase 23 voltage, B side
U31B Phase-to-phase 31 voltage, B side
UL1B Phase-to-earth 1 voltage, B side
UL2B Phase-to-earth 2 voltage, B side
UL3B Phase-to-earth 3 voltage, B side
S Apparent power
Table continues on next page
1MRS758755 A Section 3
Basic functions
REC615 and RER615 179
Technical Manual