GUID-F0078144-A40B-4A72-915A-0E6665F8DEB1 V1 EN
Figure 103: Operation in "Toggle" mode
The BLOCK input can be used for blocking the functionality of the outputs. The
operation of the BLOCK input depends on the Operation mode setting. If Operation
mode is "Toggle", the output state freezes and cannot be changed while the BLOCK
input is active. If Operation mode is "Pulsed", the activation of the BLOCK input resets
the outputs to the "False" state and further control requests are ignored while the
BLOCK input is active.
From the remote communication point of view SPCGAPC toggled
operation mode is always working as persistent mode. The output O#
follows the value written to the input IN#.
3.16.12.3 Signals
Table 176: SPCGAPC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
IN1 BOOLEAN 0=False Input of control point 1
IN2 BOOLEAN 0=False Input of control point 2
IN3 BOOLEAN 0=False Input of control point 3
IN4 BOOLEAN 0=False Input of control point 4
IN5 BOOLEAN 0=False Input of control point 5
IN6 BOOLEAN 0=False Input of control point 6
IN7 BOOLEAN 0=False Input of control point 7
IN8 BOOLEAN 0=False Input of control point 8
IN9 BOOLEAN 0=False Input of control point 9
IN10 BOOLEAN 0=False Input of control point 10
IN11 BOOLEAN 0=False Input of control point 11
IN12 BOOLEAN 0=False Input of control point 12
IN13 BOOLEAN 0=False Input of control point 13
IN14 BOOLEAN 0=False Input of control point 14
IN15 BOOLEAN 0=False Input of control point 15
IN16 BOOLEAN 0=False Input of control point 16
1MRS758755 A Section 3
Basic functions
REC615 and RER615 163
Technical Manual