IED
IEC 61850
remote
IEC 61850
station
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
IED
IEC 61850
station
L+SLOCAL STATION S+R
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
OFFL+S+R
GUID-3F4E6CD7-A89E-4057-8E25-8846B5387C82 V1 EN
Figure 101: Station authority is “L,S,S+R,L+S,L+S+R”
When station authority level “L,S,S+R,L+S,L+S+R” is used, control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input CTRL_STA are applicable
for this station authority level.
“Station” and “Local + Station” control access can be reserved by using R/L button or
CONTROL function block in combination with IEC 61850 data object
CTRL.LLN0.LocSta.
Table 170: Station authority level “L,S,S+R,L+S,L+S+R” using R/L button
L/R Control
L/R Control status Control access
R/L button
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
Local FALSE FALSE 1 x
Remote FALSE TRUE 7 x x
Remote TRUE FALSE 3 x
Local +
Remote
FALSE TRUE 6 x x x
Local +
Remote
TRUE TRUE 5 x x
Off FALSE FALSE 0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
Table 171: Station authority level “L,S,S+R,L+S,L+S+R” using CONTROL function block
L/R Control
L/R Control status Control access
Control FB input
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
CTRL_OFF FALSE FALSE 0
CTRL_LOC FALSE FALSE 1 x
CTRL_STA FALSE FALSE 3 x
Table continues on next page
Section 3 1MRS758755 A
Basic functions
158 REC615 and RER615
Technical Manual