ABB RELION Series - Three-phase directional overcurrent protection (F)DPHxPDOC

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
Operate delay time 40...200000 ms 10 40 Operate delay time
Operating curve type 1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
-1=Recloser 1
-2=Recloser 2
-3=Recloser 3
-4=Recloser 4
-5=Recloser 5
-6=Recloser 6
-7=Recloser 7
-8=Recloser 8
-9=Recloser 8+
-10=Recloser 8*
-11=Recloser 9
-12=Recloser 11
-13=Recloser 13
-14=Recloser 14
-15=Recloser 15
-16=Recloser 16
-17=Recloser 17
-18=Recloser 18
-19=Recloser A
-20=Recloser B
-21=Recloser C
-22=Recloser D
-23=Recloser E
-24=Recloser F
-25=Recloser G
-26=Recloser H
-27=Recloser J
-28=Recloser Kg
-29=Recloser Kp
-30=Recloser L
-31=Recloser M
-32=Recloser N
-33=Recloser P
-34=Recloser R
-35=Recloser T
-36=Recloser V
-37=Recloser W
-38=Recloser Y
-39=Recloser Z
15=IEC Def. Time Selection of time delay curve type
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
1MRS758755 A Section 4
Protection functions
REC615 and RER615 217
Technical Manual