GUID-CD0B7D5A-1F1A-47E6-AF2A-F6F898645640 V2 EN
Figure 124: Configurable operating sectors
Table 239: Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The value for DIR_A/_B/_C
The ANGLE_X is not in any of the defined sectors,
or the direction cannot be defined due too low
amplitude
0 = unknown
The ANGLE_X is in the forward sector 1 = forward
The ANGLE_X is in the reverse sector 2 = backward
(The ANGLE_X is in both forward and reverse
sectors, that is, when the sectors are overlapping)
3 = both
Table 240: Momentary phase combined direction value for monitored data view
Criterion for phase combined direction information
The value for DIRECTION
The direction information (DIR_X) for all phases is
unknown
0 = unknown
The direction information (DIR_X) for at least one
phase is forward, none being in reverse
1 = forward
The direction information (DIR_X) for at least one
phase is reverse, none being in forward
2 = backward
The direction information (DIR_X) for some phase
is forward and for some phase is reverse
3 = both
1MRS758755 A Section 4
Protection functions
REC615 and RER615 231
Technical Manual