Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_MULT BOOLEAN 0=False Enable signal for current multiplier
NON_DIR BOOLEAN 0=False Forces protection to non-directional
Table 245: DPHLPDOC Input signals
Name Type Default Description
I_A SIGNAL 0 Phase A current
I_B SIGNAL 0 Phase B current
I_C SIGNAL 0 Phase C current
I
2
SIGNAL 0 Negative phase sequence current
U_A_AB SIGNAL 0 Phase-to-earth voltage A or phase-to-phase
voltage AB
U_B_BC SIGNAL 0 Phase-to-earth voltage B or phase-to-phase
voltage BC
U_C_CA SIGNAL 0 Phase-to-earth voltage C or phase-to-phase
voltage CA
U
1
SIGNAL 0 Positive phase sequence voltage
U
2
SIGNAL 0 Negative phase sequence voltage
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_MULT BOOLEAN 0=False Enable signal for current multiplier
NON_DIR BOOLEAN 0=False Forces protection to non-directional
Table 246: DPHHPDOC Input signals
Name
Type Default Description
I_A SIGNAL 0 Phase A current
I_B SIGNAL 0 Phase B current
I_C SIGNAL 0 Phase C current
I
2
SIGNAL 0 Negative phase sequence current
U_A_AB SIGNAL 0 Phase-to-earth voltage A or phase-to-phase
voltage AB
U_B_BC SIGNAL 0 Phase-to-earth voltage B or phase-to-phase
voltage BC
U_C_CA SIGNAL 0 Phase-to-earth voltage C or phase-to-phase
voltage CA
U
1
SIGNAL 0 Positive phase sequence voltage
U
2
SIGNAL 0 Negative phase sequence voltage
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_MULT BOOLEAN 0=False Enable signal for current multiplier
NON_DIR BOOLEAN 0=False Forces protection to non-directional
1MRS758755 A Section 4
Protection functions
REC615 and RER615 241
Technical Manual