Protected feeder
Background network
Im(Yo)
Re(Y
o)
Reverse fault:
Y
o -j*I
eFd
/U
ph
GUID-B852BF65-9C03-49F2-8FA9-E958EB37FF13 V1 EN
Figure 167: Admittance calculation during a reverse fault
R
CC
Resistance of the parallel resistor
L
CC
Inductance of the compensation coil
R
n
Resistance of the neutral earthing resistor
Y
Fd
Phase-to-earth admittance of the protected feeder
Y
Bg
Phase-to-earth admittance of the background network
For example, in a 15 kV compensated network with the magnitude of the earth-fault
current in the protected feeder being 10 A (Rf = 0 Ω), the theoretical value for the
measured admittance during an earth fault in the reverse direction, that is, outside the
protected feeder, can be calculated.
Yo j
I
U
j
A
kV
j
eFd
ph
= =
10
15 3
1 15. milliSiemens
GUID-E2A45F20-9821-436E-94F1-F0BFCB78A1E3 V1 EN
(Equation 15)
Section 4 1MRS758755 A
Protection functions
330 REC615 and RER615