Figure 171: Admittance characteristic with different operation modes when
Directional mode = "Reverse"
Timer
Once activated, the timer activates the START output. The time characteristic is
according to DT. When the operation timer has reached the value set with the Operate
delay time setting, the OPERATE output is activated. If the fault disappears before the
module operates, the reset timer is activated. If the reset timer reaches the value set
with the Reset delay time setting, the operation timer resets and the START output is
Section 4 1MRS758755 A
Protection functions
338 REC615 and RER615