EasyManua.ls Logo

ABB RELION Series - Page 499

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
either given in ohm/km and section length in km, or ohm/mile and section length in
miles. The resulting Flt distance matches the units entered for the line section lengths.
Positive-sequence impedance values
Fault location requires accurate setting values for line impedances. Positive-sequence
impedances are required both for location of short circuits and earth faults. As data
sheet impedance per unit values are generally valid only for a certain tower
configuration, the values should be adjusted according to the actual installation
configuration. This minimizes the fault location errors caused by inaccurate settings.
The positive-sequence reactance per unit and per phase can be calculated with a
following approximation equation which applies to symmetrically transposed three-
phase aluminium overhead lines without ground wires.
X
a
r
km
n
en
1
4
10 2 0 5 +
ω
ln . [ / ]
GUID-B7F3697A-7C8E-4BF6-A63C-7BFD307DD128 V2 EN (Equation 59)
ω
n
2 × π × f
n
, where f
n
= fundamental frequency [Hz]
a
en
a a a
12 23 31
3
( )
GUID-DA850ABF-239A-4AB5-B63B-F0B54557CF2E V2 EN
the geometric average of phase distances [m]
a
xy
distance [m] between phases x and y
r radius [m] for single conductor
GUID-40949A85-D97F-4639-9D61-3CAE997D28D3 V2 EN
Figure 255: Typical distribution line tower configurations
Example values of positive-sequence impedances for typical medium voltage
overhead-lines are given in the following tables.
Table 515: Positive-sequence impedance values for typical 11 kV conductors, “Flat” tower
configuration assumed
Name
R1 [Ω/km] X1 [Ω/km]
ACSR 50 SQ.mm 0.532 0.373
ACSR 500 SQ.mm 0.0725 0.270
1MRS758755 A Section 5
Protection related functions
REC615 and RER615 493
Technical Manual

Table of Contents

Other manuals for ABB RELION Series

Related product manuals