EasyManua.ls Logo

ABB RELION Series - Page 570

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
LOW_ALARM BOOLEAN 0=False
1=True
Low alarm
I_INST_A FLOAT32 0.00...40.00 xIn IL1 Amplitude,
magnitude of
instantaneous value
I_ANGL_A
FLOAT32 -180.00...180.00 deg IL1 current angle
I_DB_A FLOAT32 0.00...40.00 xIn IL1 Amplitude,
magnitude of reported
value
I_DMD_A
FLOAT32 0.00...40.00 xIn Demand value of IL1
current
I_RANGE_A Enum 0=normal
1=high
2=low
3=high-high
4=low-low
IL1 Amplitude range
I_INST_B FLOAT32 0.00...40.00 xIn IL2 Amplitude,
magnitude of
instantaneous value
I_ANGL_B
FLOAT32 -180.00...180.00 deg IL2 current angle
I_DB_B FLOAT32 0.00...40.00 xIn IL2 Amplitude,
magnitude of reported
value
I_DMD_B
FLOAT32 0.00...40.00 xIn Demand value of IL2
current
I_RANGE_B Enum 0=normal
1=high
2=low
3=high-high
4=low-low
IL2 Amplitude range
I_INST_C FLOAT32 0.00...40.00 xIn IL3 Amplitude,
magnitude of
instantaneous value
I_ANGL_C
FLOAT32 -180.00...180.00 deg IL3 current angle
I_DB_C FLOAT32 0.00...40.00 xIn IL3 Amplitude,
magnitude of reported
value
I_DMD_C
FLOAT32 0.00...40.00 xIn Demand value of IL3
current
I_RANGE_C Enum 0=normal
1=high
2=low
3=high-high
4=low-low
IL3 Amplitude range