GUID-58B6C3F2-873A-4B13-9834-9BB21FCA5704 V1 EN
Figure 17: Symbols used in the sequence diagrams
"Follow-S": Follow Signal, ON
In this mode ALARM follows the input signal value, Non-latched.
Activating
signal
LED
GUID-952BD571-874A-4572-8710-F0E879678552 V1 EN
Figure 18: Operating sequence "Follow-S"
"Follow-F": Follow Signal, Flashing
Similar to "Follow-S", but instead the LED is flashing when the input is active, Non-
latched.
"Latched-S": Latched, ON
This mode is a latched function. At the activation of the input signal, the alarm shows
a steady light. After acknowledgement by the local operator pressing any key on the
keypad, the alarm disappears.
Activating
signal
LED
Acknow.
GUID-055146B3-780B-43E6-9E06-9FD8D342E881 V1 EN
Figure 19: Operating sequence "Latched-S"
"LatchedAck-F-S": Latched, Flashing-ON
This mode is a latched function. At the activation of the input signal, the alarm starts
flashing. After acknowledgement, the alarm disappears if the signal is not present and
gives a steady light if the signal is present.
Section 3 1MRS758755 A
Basic functions
52 REC615 and RER615
Technical Manual