EasyManua.ls Logo

ABB RELION Series - Insulation tests

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description Type test value Reference
Pulse magnetic field immunity
test
1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic
field immunity test
IEC 61000-4-10
2 s 100 A/m
1 MHz 400 transients/s
Power frequency immunity test Binary inputs only IEC 61000-4-16
IEC 60255-26, class A
Common mode 300 V rms
Differential mode 150 V rms
Emission tests EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 22
Conducted
0.15...0.50 MHz <79 dB (µV) quasi peak
<66 dB (µV) average
0.5...30 MHz <73 dB (µV) quasi peak
<60 dB (µV) average
Radiated
30...230 MHz <40 dB (µV/m) quasi peak,
measured at 10 m distance
230...1000 MHz <47 dB (µV/m) quasi peak,
measured at 10 m distance
Table 748: Insulation tests
Description
Type test value Reference
Dielectric tests 2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min,
communication
IEC 60255-27
Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
IEC 60255-27
Insulation resistance
measurements
>100 MΩ, 500 V DC IEC 60255-27
Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC 60255-27