Description Type test value Reference
Pulse magnetic field immunity
test
1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic
field immunity test
IEC 61000-4-10
• 2 s 100 A/m
• 1 MHz 400 transients/s
Power frequency immunity test Binary inputs only IEC 61000-4-16
IEC 60255-26, class A
• Common mode 300 V rms
• Differential mode 150 V rms
Emission tests EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 22
• Conducted
0.15...0.50 MHz <79 dB (µV) quasi peak
<66 dB (µV) average
0.5...30 MHz <73 dB (µV) quasi peak
<60 dB (µV) average
• Radiated
30...230 MHz <40 dB (µV/m) quasi peak,
measured at 10 m distance
230...1000 MHz <47 dB (µV/m) quasi peak,
measured at 10 m distance
Table 748: Insulation tests
Description
Type test value Reference
Dielectric tests 2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min,
communication
IEC 60255-27
Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
IEC 60255-27
Insulation resistance
measurements
>100 MΩ, 500 V DC IEC 60255-27
Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC 60255-27
Section 15 1MRS758755 A
Protection relay and functionality tests
788 REC615 and RER615
Technical Manual