Chapter 2 Parameter Descriptions
Ground Fault Warning Threshold
Linear Number: P229
Default Value: 8.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Ground Fault Warning.
Ground Fault Trip Threshold
Linear Number: P230
Default Value: 15.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Ground Fault Trip.
Filter Time For Overspeed Fault (Upper Limit)
Linear Number: P231
Default Value: 100
Minimum Value: 0
Maximum Value: 32767
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the upper limit for Filter Time For Overspeed Fault.
Overspeed occurs when speed is greater than Threshold Of Over-Speed Fault At
Upper Frequency Limit (P234).
Filter Time For Overspeed Fault (Lower Limit)
Linear Number: P232
Default Value: 100
Minimum Value: 0
Maximum Value: 32767
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the lower limit for Filter Time For Overspeed Fault.
Overspeed occurs when speed is greater than Threshold Of Over-Speed Fault At
Lower Frequency Limit (P233).