Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 145
Parameter Descriptions Chapter 2
Output Voltage Deviation Fault Threshold
Linear Number: P224
Default Value: 80.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Output Voltage Deviation Fault.
Output Voltage Abnormality Warning Cancellation Threshold
Linear Number: P226
Default Value: 50.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Output Voltage Abnormality Warning
Cancellation.
Ground Fault Detection Scaling Correction Factor
Linear Number: P227
Default Value: 100.00%
Minimum Value: 0.00%
Maximum Value: 199.99%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Ground Fault Detection Scaling Correction Factor.
Filter Time For Ground Fault
Linear Number: P228
Default Value: 1000 ms
Minimum Value: 0 ms
Maximum Value: 32767ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the filter time for the Ground Fault.