144 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Motor Overload Time
Linear Number: P217
Default Value: 60 s
Minimum Value: 0 s
Maximum Value: 32767 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Motor Overload Time.
Filter Time For Output Over Voltage
Linear Number: P221
Default Value: 100 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the filter time for the Output Over Voltage.
Output Over Voltage Fault Threshold
Linear Number: P222
Default Value: 120.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Output Over Voltage Fault.
Output Voltage Deviation Warning Threshold
Linear Number: P223
Default Value: 60.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Output Voltage Deviation Warning.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals