Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 143
Parameter Descriptions Chapter 2
Output Short-Circuit Fault Threshold
Linear Number: P213
Default Value: 179.99%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Output Short-Circuit Fault.
Motor Minimum Overload Current
Linear Number: P214
Default Value: 104.99%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the minimum over load current for the motor.
Motor Overload Cycle Time
Linear Number: P215
Default Value: 600 s
Minimum Value: 0 s
Maximum Value: 32767 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Motor Overload Cycle Time.
MotorOverload Trip Threshold
Linear Number: P216
Default Value: 120.00%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the MotorOverload Trip.