142 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Phase Over Current Filter Time
Linear Number: P209
Default Value: 5
Minimum Value: 0
Maximum Value: 32767
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the time for the Phase Over Current Filter.
Phase Over Current Threshold
Linear Number: P210
Default Value: 179.99
Minimum Value: 0.00
Maximum Value: 399.99
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Phase Over Current.
Filter Time For Abnormal Output Voltage
Linear Number: P211
Default Value: 1000 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the filter time for the Abnormal Output Voltage.
Filter Time For Output Short-Circuit
Linear Number: P212
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the filter time for the Output Short-Circuit.