Parameter Descriptions Chapter 2
Line Current Negative Sequence Filter Time
Linear Number: P175
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the time for the Line Current Negative Sequence Filter.
Line Current Negative Sequence Fault Threshold
Linear Number: P176
Default Value: 100.00%
Minimum Value: 0.00%
Maximum Value: 199.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Line Current Negative Sequence Fault.
Line Current Negative Sequence Fault Delay
Linear Number: P177
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the Line Current Negative Sequence Fault.
Phase Over Current Enable Frequency Range Upper Limit
Linear Number: P208
Default Value: 10
Minimum Value: 0
Maximum Value: 100
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the upper limit for the Phase Over Current Enable Frequency
Range.