140 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Line Current Filter Time
Linear Number: P168
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the time for the Line Current Filter.
Line Short Circuit Fault Threshold
Linear Number: P169
Default Value: 180%
Minimum Value: 0%
Maximum Value: 400%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Line Short Circuit Fault.
Line Short Circuit Fault Delay
Linear Number: P170
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the Line Short Circuit Fault.
Line Current Positive Sequence Filter Time
Linear Number: P174
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the time for the Line Current Positive Sequence Filter.