148 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Frequency Deviation Warning Delay
Linear Number: P237
Default Value: 8 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the Frequency Deviation Warning.
Motor Stall Fault Threshold
Linear Number: P238
Default Value: 10.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Motor Stall Fault.
Motor Stall Fault Delay
Linear Number: P239
Default Value: 6000 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the Motor Stall Fault.
Transformer Over Temperature Fault Delay
Linear Number: P240
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the Transformer Over Temperature Fault.