Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 149
Parameter Descriptions Chapter 2
Transformer Over Temperature Warning Delay
Linear Number: P241
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the Transformer Over Temperature Warning.
DC Bus Under Voltage Fault Threshold
Linear Number: P254
Default Value: 63%
Minimum Value: 0%
Maximum Value: 100 %
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the DC bus under voltage fault.
Ground Fault Warning Cancellation Threshold
Linear Number: P256
Default Value: 5.00 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Ground Fault Warning Cancellation.
Motor Stall Warning Cancellation Threshold
Linear Number: P257
Default Value: 2.98 pu
Minimum Value: 0.00 pu
Maximum Value: 199.99 pu
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Motor Stall Warning Cancellation.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals