150 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
DC Bus Under Voltage Fault Delay
Linear Number: P258
Default Value: 1000 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the DC bus under voltage fault.
DC Bus Voltage Deviation Fault Threshold
Linear Number: P266
Default Value: 25%
Minimum Value: 0%
Maximum Value: 100%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the DC bus voltage deviation fault.
DC Bus Voltage Deviation Fault Filter Time
Linear Number: P267
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 1000 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the filter time for the DC bus voltage deviation fault.
DC Bus Under Voltage Warning Threshold
Linear Number: P274
Default Value: 80%
Minimum Value: 0%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the DC bus under voltage warning.