Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 71
Parameter Descriptions Chapter 2
Modulation Index
Linear Number: P455
Default Value: 84.0% (2.3 kV), 87.6% (2.4 kV),
77.3% (3.0 kV), 85.0% (3.3 kV),
83.8% (4.0 kV), 87.0% (4.16 kV),
87.0% (6.0 kV), 81.0% (6.3 kV),
85.0% (6.6 kV), 83.7% (6.9 kV),
91% (10.0 kV)
89% (11.0 kV)
Minimum Value: 0%
Maximum Value: 110%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Modulation Index.
Motor Voltage Upper Limit
Linear Number: P456
Default Value: 84.0% (2.3 kV), 87.6% (2.4 kV),
77.3% (3.0 kV), 85.0% (3.3 kV),
83.8% (4.0 kV), 87.0% (4.16 kV),
87.0% (6.0 kV), 81.0% (6.3 kV),
85.0% (6.6 kV), 83.7% (6.9 kV),
91% (10.0 kV)
89% (11.0 kV)
Minimum Value: 0%
Maximum Value: 110%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Motor Voltage Upper Limit.
Coefficient A
Linear Number: P458
Default Value: 40%
Minimum Value: 0%
Maximum Value: 100%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the Coefficient A.