Chapter 4: AC Drive Parameters
Page 4–85
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Type Hex Addr Dec Addr
P3.44 Final Counter Value
♦R/W 032C 40813
Range/Units Default
0~65500
0
The counter trigger can be incremented by the Multi-Function Input Terminal DI6 (set P3.08
to 23). Once the counter has reached the value in P3.44, the specified output terminal will be
activated (any Multi-Function Output = 18). When the final count trigger is deactivated the count
automatically returns to 0.
Type Hex Addr Dec Addr
P3.45 Mid-point Counter Value
♦R/W 032D 40814
Range/Units (Format: 16-bit unsigned) Default
0~65500
0
When the counter value reaches the value set in this parameter, the corresponding Multi-Function
Output Terminal (set to 17) will be activated only for that count. Once DI6 is triggered again to the
next count, the associated output terminal will be deactivated, as shown below.
1.0 ms
minimum width of trigger signal
1.0 ms
c0000 c0001 c0002 c0003 c0004 c0005
c0000
c0001 c0002
P3.45=3
P3.44=5
Final Count Value
R2 (P3.18=18)
(output signal)
Mid-point Counter Value
R1 (P3.17=17)
Display Value (P8.00=1)
TRG (P3.08=23)
Counter Trigger