Page B–16
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Appendix B: Optional I/O and Communication Cards
gs4-Cm-eneTip speCifiCaTions
feaTures
•
Auto-detects transmission speed 10/100 Mbps
•
MDI/MDI-X auto-detect
•
Supports MODBUS TCP slave communication protocol (1 connection)
•
On-line monitoring
•
Supports Ethernet/IP explicit message Class 3
•
EtherNet/IP implicit Class 1
GS4-CM-ENETIP Specifications
Network Interface
Interface
RJ45 with Auto MDI/MDIX
Number of ports
1 Port
Transmission method
IEEE 802�3, IEEE 802�3u
Transmission cable
Category 5e shielding 100M
Transmission speed
10/100 Mbps Auto-Detect
Network protocol
ICMP, IP, TCP, UDP, DHCP, Modbus TCP
Electrical
Power supply voltage
5VDC (supplied by the AC motor drive)
Insulation voltage
2kV
Power consumption
0�8W
Weight
25g
Environment
Noise immunity
ESD (IEC 61800-5-1, IEC 61000-4-2)
EFT (IEC 61800-5-1, IEC 61000-4-4)
Surge Test (IEC 61800-5-1, IEC 61000-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 61000-4-6)
Operation / storage
Operation: -10°C~50°C [14°F~122°F] (temperature), 90% (humidity)
Storage: -25°C~70°C [-13°F~158°F] (temperature), 95% (humidity)
Vibration / shock
immunity
International standard: IEC 61800-5-1, IEC 60068-2-6/IEC 61800-5-1, IEC 60068-2-
27
CirCuiT board layouT
Front Back
1
2
1
1
7
4
6
2
2
5
3
1)
Mounting screw hole (qty: 2)
2)
Positioning hole (qty: 2)
3)
GS4 AC drive connection port
4)
LINK LED indicator
5)
RJ45 port
6)
POWER LED indicator
7)