Appendix C: Digital and Analog I/O Parameter Maps
Page C–11
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
gs4 analOg OUtPUt 1 ParaMeters
GS4 – AO1 Specific Parameters
Parameter Selection / Value Default
User
Selection
Terminals AO1 – ACM N/A N/A
PLC Address D1040 N/A N/A
P4.50
Analog Output 1 (AO1)
0: Output Frequency (Hz)
1: Frequency Command (Hz)
2: Motor Speed (Hz)
3: Output Current (rms)
4: Output Voltage
5: DC Bus Voltage
6: Power Factor
7: Power
8: AI1
9: AI2
10: AI3
11: As 485 AO
12: As COM Card AO
13: Fixed Value
0
P4.51
AO1 Gain 0�0~500�0% 100�0
P4.52
AO1 Negative Value Handle
0: Absolute Value
1: 0V When Negative
2: Offset 5V = 0 Value
0
P4.53
AO1 0~20mA/4~20mA Selection
0: 0~20mA
1: 4~20mA
0
P4.60
AO1 Output Constant Level 0�00~100�00% 0�00
P4.62 Bit 0
PLC Analog Output Mask
0: Drive Controlled
1: PLC Controlled
0
gs4 analOg OUtPUt 2 ParaMeters
GS4 – AO2 Specific Parameters
Parameter Selection / Value Default
User
Selection
Terminals AO2 – ACM N/A N/A
PLC Address D1045 N/A N/A
P4.54
Analog Output 2 (AO2)
0: Output Frequency (Hz)
1: Frequency Command (Hz)
2: Motor Speed (Hz)
3: Output Current (Arms)
4: Output Voltage (V)
5: DC Bus Voltage (V)
6: Power Factor (%)
7: Power (% Rated)
8: AI1 (%)
9: AI2 (%)
10: AI3 (%)
11: As 485 AO
12: As COM Card AO
13: Fixed Value
0
P4.55
AO2 Gain 0�0~500�0% 100�0
P4.56
AO2 Negative Value Handle
0: Absolute Value
1: 0V When Negative
2: Offset 5V = 0 Value
0
P4.57
AO2 0~20mA/4~20mA Selection
0: 0~20mA
1: 4~20mA
0
P4.59
AO2 Offset (Bias) -100�00% to +100�00% 0�00
P4.61
AO2 Output Constant Level 0�00~100�00% 0�00
P4.62 Bit 1
PLC Analog Output Mask
0: Drive Controlled
1: PLC Controlled
0