Page 4–88
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P3.49 PLC – Digital Output Mask
Read 0331 40818
Range/Units (Format: 16-bit binary) Default
0~65535
0
P3.49 shows the external Multi-Function Output terminals that are controlled by the PLC.
Bit
2
0
0
2
6
6
2
13
13
2
15
15
2
14
14
2
12
12
2
11
11
2
10
10
2
8
8
2
9
9
2
7
7
2
5
5
2
4
4
2
3
3
2
2
2
2
1
1
Relay1
Relay2
reserved
DO1
DO2
DO10/RO10
DO11/RO11
RO12
RO13
RO14
Terminal
Address
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y10
Y11
Function
R1 Relay Output
R2 Relay Output
reserved
DO1 Output
DO2 Output
DO10/RO10 Output
DO11/RO11 Output
RO12 Output
RO13 Output
RO14 Output
For
Card
Example: If the value of P3.49 displays 0003h (Hex), it means R1and R2 are used by PLC.
Display Value
3 = 2 + 1
= 1x2
1
+ 1x2
0
= bit
1
x2
1
+ bit
0
x2
0
Weight
Bit
2
0
1
2
6
0
2
7
0
2
5
0
2
4
0
2
3
0
2
2
0
2
1
1
0 = NOT used by PLC
1 = USED by PLC
Relay1
Relay2
reserved
DO1
DO2
DO10/RO10
DO11/RO11
Type Hex Addr Dec Addr
P3.50 Increase/Decrease Speed Command Record
Read 0332 40819
Range/Units (Format: 16-bit unsigned) Default
0~600�00
60�00
When the source of frequency command comes from the external terminal and a fault occurs at
this time, the frequency command of the external terminal will be saved in this parameter. (Not
the actual current frequency of the drive at time of fault, just the last commanded frequency.)