Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P3.52 Desired Current
♦R/W 0334 40821
Range/Units Default
0~150% of GS4 VT current rating
0
Output Current Level Setting for Multi-Function Output Terminals.
When output current to the motor is greater than or equal to P3.52, it will activate the
Multi-Function Output terminal that is set to 27 (Above Current Output).
When output current to the motor is less than P3.52, it will activate Multi-Function Output
terminal that is set to 28 (Below Current Output).
NOTE: The % of Desired Current P3.52 is based on the Drive's VT Current Rating (not motor current
rating).
Related parameters: P3.51, P3.53 (refer to P3.51, page 4–89).
Type Hex Addr Dec Addr
P3.53 Output Frequency Limit for Multi-Function Output Terminals
♦R/W 0335 40822
Range/Units (Format: 16-bit unsigned) Default
0�00~600�00 Hz
0
When a Multi-Function Output setting = #42 (Brake Released at Stop), the output will activate
when the drive is stopped and decels past P3.53. In this mode, the output will only stay on for the
time in P3.51 (Brake Delay Time). With a long decel ramp and a short brake time, the output could
energize (for P3.51 seconds) and then de-energize before the deceleration ramp is complete.
•
When a Multi-Function Output setting = #58 (Frequency Output Above P3�53), the output will
activate when the drive's output frequency is ≥ P3.53.
•
When a Multi-Function Output setting = #59 (Frequency Output Below P3�53), the output will
activate when the drive's output frequency is < P3�53�
Related parameters: P3.51, P3.52 (refer to P3.51, page 4–89).
Type Hex Addr Dec Addr
P3.54 reserved
n/a 0336 40823
Range/Units Default
n/a
n/a
Type Hex Addr Dec Addr
P3.55 reserved
n/a 0337 40824
Range/Units Default
n/a
n/a