Page 4–110
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P4.60 AO1 Output Constant Level
R/W 043C 41085
P4.61 AO2 Output Constant Level
R/W 043D 41086
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
0�00
The Parameter memory can only be written to 10
9
times before a memory error will occur. This
memory error will not occur if using P4.50/P4.54 setting #11 or #12.
Use P4�50/P4�54 setting #11 or #12 if the AO value will be changed frequently
Use P4�50/P4�54 setting #13 if the value will not be changed frequently
The analog outputs can be set to fixed levels through communications, keypad, etc.
To use AO1, P4�50 must be set for 13: Fixed Value�
To use AO2, P4�54 must be set for 13: Fixed Value�
For P4.50/P4.54 Setting #13: Fixed Value
Adjust the value of P4�60 via the keypad to increase or decrease the analog output� Writing to
P4�60 via RS-485 or Ethernet does change the output value�
If writing via comms, the values are 0~10000 for 0.00~100.00% gains.
P4�51/P4�55 Gain = 100%
P4.52/P4.56 Negative Value Handle ≠ 2
P4�53/P4�57 AOx mA Selection = 0~20mA
Type Hex Addr Dec Addr
P4.62 PLC Analog Output Mask
♦R/W 043E 41087
Range/Units (Format: 16-bit unsigned) Default
0 to 65535
0
P4.62 shows the external Analog Output terminals that are controlled by the PLC.
Example: If the value of P4.62 displays 0002h(Hex), it shows that AO1 is controlled by the drive and
AO2 is controlled by the PLC.
0 0 0 0 0 0 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Display Value:
2 = 1x2
1
+ 0x2
0
= bit 1x2
1
+ bit 0x2
0
Weights
Bits
AO1
AO2
0 = ON; controlled by drive
1 = OFF; controlled by PLC