EasyManua.ls Logo

Automation Direct DURApulse GS4 - Page 341

Automation Direct DURApulse GS4
542 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6: Maintenance and Troubleshooting
Page 6–9
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Warning Codes (continued)
Display on GS4-KPD Keypad
Warning
Code in
2108h
Active
Warning
Descriptions
LOCAL
Warning
SE1
Save Error 1
7
Keypad COPY error 1
Keypad transfer (check) error, including communication delays, communication
error (keypad received error FF86) and parameter value error
P9�06 must be set to 1 for a keypad to drive copy
LOCAL
Warning
SE2
Save Error 2
8
Keypad COPY error 2
Keypad transfer (check) done, parameter write error
LOCAL
Warning
oH1
Over heat 1 warn
9
IGBT over-heating warning
LOCAL
Warning
oH2
Over heat 2 warn
10
Capacitor over-heating warning
LOCAL
Warning
PID
PID FBK Error
11
PID feedback error
LOCAL
Warning
ANL
Analog Loss
12
AIx 4~20mA Signal Loss
AI1 or AI2 signal drops below 4mA when P4�05 or P4�06 are set to 1 (4~20mA)�
Enabled with P4�63 and P4�64 (AIx 4~20mA Loss Detection)�
LOCAL
Warning
uC
Under Current
13
Low current
LOCAL
Warning
AUE
Auto-tune Error
14
Auto tuning error
n/a 15~18
reserved
(continued next page)