Chapter 6: Maintenance and Troubleshooting
Page 6–25
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Fault Name
Fault Code
in Status
Monitor 1
Fault
Descriptions
Corrective Actions
Can be
Bypassed
in Fire
Mode
(Yes / no)
LOCAL
Fault
FStp
PLC Force Stop
90
If the GS4 drive is running in PLC mode, parameter P3�00 is equal to
1, 3 or 5, and Remote Operation is selected; or parameter P3�01 is
equal to 1, 3, or 5, and Local operation is selected, the drive can be
forced to stop by pressing the STOP key on the keypad�
no
n/a 91~96
reserved n/a n/a
LOCAL
Fault
CD10
Card TimeOut
97
Ethernet
communication
has not been
received from the
external controller
(within the
Ethernet Timeout
window)�
Initiate Ethernet communications from the
master controller again, or Disable checking for
Ethernet Timeout in P9�94�
n/a 98
reserved n/a n/a
LOCAL
Fault
TRAP
CPU Command Err
99
CPU trap error
Should a CPU Trap error fault persist, please
send the drive back to the factory for evaluation�
no
n/a 100~111
reserved n/a n/a