EasyManua.ls Logo

Automation Direct DURApulse GS4 - Page 389

Automation Direct DURApulse GS4
542 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 8: GSLogic Introduction
Page 8–15
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Select “Setting” to choose the communication settings to be used. To adjust communication
settings on an existing project, go to the Communication menu and select “Communication
Settings.” These PLC communication settings must be the same as the Drives Modbus settings
found in P9.01 and P9.02.
Communication Setting: Perform settings in accordance with the desired communications
method. The Default Station Address for the PLC is 2. (The Modbus station address must be
different from the GS4 Drive’s station address. The Drive’s default address =1.)
Click “OK” after completing settings to return to program editing in ladder diagram mode.

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Related product manuals