Install Telecommunications Cabling
Patch Cord/Jumper Installation and Administration
SI Installation and Upgrades 445
June 2004
Install Coupled Bonding Conductor
Return to Task List
The Figure 165, Coupled Bonding Conductor, on page 446 (CBC) connects to the single-point ground
block and runs adjacent to pairs in an associated telecommunications cable. The mutual coupling between
the bonding conductor and the pairs reduces potential differences in terminating equipment.
1 Cut a 10 AWG (#25) (2.5 mm
2
) wire long enough to reach from the system’s single-point ground
block or DC power cabinet Ground Discharge Bar to the MDF CBC block.
2 Connect one end of the 10 AWG (#25) (2.5 mm
2
) wire to the single-point ground block (or
Ground Discharge Bar).
3 Route the wire next to the 25-pair cables connecting to the trunk/auxiliary (purple) field.
4 Tie wrap the 10 AWG (#25) (2.5 mm
2
) wire to the 25-pair cables.
5 Connect the 10 AWG (#25) (2.5 mm
2
) wire to the MDF CBC ground block.
6 Repeat the above steps for each CBC ground wire installed.