THOR Access Control
October 1, 1995 18-006/081-04 GB
30
75 - Set/unset control DC Is used for setting/unsetting of other alarm systems (not THOR). Is
activated by pressing the set push button as described in the Operating
Procedures. Is reset by pressing the unset push button. Both set and
unset are logged.
76 - Set/unset control pulsed Is used for setting/unsetting of other alarm systems (not THOR). Gives a
5 sec. pulse when pressing the set or unset push button as described in
the Operating Procedures. Only activating type 7 and 8 can be used
together with this softtype. Both set and unset are logged.
78 - All cards out The output is active if all cards are registered in zone 00. The output is
passive if only one card is not in zone 00.
79 - Alarm shunt Output used to bypass a door contact connected to an external alarm
system. Is activated when input softtype 80 is activated and reset 1 sec.
after the door is closed again (input softtype 30).
80 - Battery test Is used to control battery load in connection with battery test. Is activated
15 seconds every 24 hour or when the menu 96 "Battery Test" is called.
83 - Door released Output for striking plate. Is activated when input softtype 80 is active.
MUST be used with activating type 1 or 2. (duration is controlled by the
door release time).
84 - Door release door 2 Output for striking plate for door 2. Is activated when input softtype 81 is
active. MUST be used with activating type 1 or 2. (duration is controlled
by the door release time programmed for door 1).
86 - External release Is activated when the striking plate output (door 1) is released. Is reset
when the door is closed again or by time-out (door release time). Is
normally connected to input softtype 61 on the corresponding reader on
another bus.
90 - 94 - THEN output For IF/THEN rules. Can be used to implement special functions. An
expression is programmed for each softtype (see the section for IF/THEN
rules.
The softtypes 90-94 are activated when the "IF" expression changes
status from "FALSE" to "TRUE". The output will be reset by the next door
release with card, or time out as specified by the activating type.
95 - 97 - THEN output For IF/THEN rules. Can be used to implement special functions. An
expression is programmed for each softtype (see the section for IF/THEN
rules.
The softtypes 95-98 are active when the "IF" expression is "TRUE". The
output will be reset when the "IF" expression is false, or time out as
specified in the activating type.
98 - THEN output Similar to the output softtypes 95 to 97. The only difference is that
softtype 98 suppresses a DOOR FORCED/DOOR HELD message if the
output is used in an IF/THEN equation which includes the input softtype
80 (door striking plate).