CEEC300 Function Block
Memory tab
R301.1 Experion C300 Controller User's Guide 115
11/06 Honeywell
Plain Text Parameter Name
User
Configurable
Notes
Previous Hour Cycle
Overruns
LSCYCLEOVRN
[0…39]
No
A count of cycle
overruns that have
occurred during the
previous hour.
Memory tab
The Memory tab contains data on general memory usage in the C300. It also shows
memory usage parameters in terms of internal memory units: descriptors and blocks.
The following table summarizes the parameter data you can monitor on the Memory tab
of the configuration form for the selected CEEC300 block.
Plain Text Parameter Name
User
Configurable
Notes
Memory Usage in KBytes
Total User
Memory(kb)
TOTALMEMINK
No
Shows the total size of
CEE user memory pool,
in kilobytes.
Currently Used
Memory(kb)
USEDMEMINK
No
The total amount of
used memory in CEE
user memory pool, in
kilobytes.
Currently Free
Memory(kb)
FREEMEMINK
No
Amount of free memory
in CEE user memory
pool, in kilobytes.
Largest Free Memory
Block Size(kb)
MAXFREEINK
No
The size of largest
contiguous memory
block in CEE user
memory pool, in
kilobytes.
Memory Usage in Bytes
Total User
Memory(b)
TOTALMEM
No
Total size of CEE user
memory pool, in bytes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion C300 and is the answer not in the manual?

Honeywell Experion C300 Specifications

General IconGeneral
Controller TypeProcess Controller
Communication ProtocolsFoundation Fieldbus, HART
Power Supply24V DC
RedundancyOptional
Mounting OptionsDIN Rail
CertificationsFM

Related product manuals