Configure a Secondary C300 Controller block
To configure a CEEC300 function block
46 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Step Action Result
23
Accept default or click
down-arrow
button to select another value specific to
the given environment. Press <Tab>.
Moves cursor to Store Expiration Time
column.
24
Accept the default or key in desired
value. Click Server History tab.
Calls up the Server History configuration
form.
25
Use the on-line help as a guide to
complete the configuratrion entries on
this tab. Click on the Server Displays
tab.
Calls up the Server Displays
configuration form.
26
Use the on-line help as a guide to
complete the configuratrion entries on
this tab. Click the OK button.
Closes the form.
This completes the configuration
procedure for C300CEE block.
REFERENCE - INTERNAL
See the Experion Control Builder Components Reference, Component
Categories and Types and the Experion Planning Guide
Configure a Secondary C300 Controller block
When a C300 Controller is configured as Redundant, the Secondary C300 Controller
block is added to the Project tab automatically.
Prerequisites
Control Builder is running
Tree windows are open
Considerations
All illustrations used in the procedure are for example purposes only.