Initiating Switchover command
Commanding Become Primary
R301.1 Experion C300 Controller User's Guide 179
11/06 Honeywell
Commanding Become Primary
Step Action
1
In the Monitoring tab, double-click the secondary C300 icon to call up its
Parameters configuration form.
2
Click the Redundancy tab to display it.
3
Click the Become Primary button.
4
Click the Yes button to confirm the action and issue the Become Primary
command.
5
Confirm that the Secondary C300 Controller assumes the Primary role
6
Click the OK button to close the Parameters form.
7
This completes the procedure.
Initiating Switchover command
You can use the following procedure to initiate a switchover command manually to a
redundant C300 Controller pair.
Prerequisites
• You can view active redundant C300 Controller pair on the Monitoring tab in
Control Builder.
• The primary and secondary C300 Controllers are synchronized.
Commanding a switchover
Step Action
1
In the Monitoring tab, double-click the primary C300 icon to call up its
Parameters configuration form.
2
Click the Redundancy tab to display it.
3
Click the Initiate Switchover button.
4
Click the Yes button to confirm the action and issue the switchover
command.
5
Confirm that the Secondary C300 Controller assumes the Primary role. The
old primary controller should boot up in the backup role.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion C300 and is the answer not in the manual?

Honeywell Experion C300 Specifications

General IconGeneral
BrandHoneywell
ModelExperion C300
CategoryController
LanguageEnglish

Related product manuals