Convert a non-redundant C300 Controller to a redundant controller
To convert a non-redundant C300 Controller to a Redundant controller
R301.1 Experion C300 Controller User's Guide 49
11/06 Honeywell
Convert a non-redundant C300 Controller to a redundant
controller
You can convert a single non-redundant C300 Controller to a redundant controller simply
by configuring the controller as redundant. The controller icon which represents the
secondary controller is then added to the Project tab.
Prerequisites
Control Builder is running
Tree windows are open
Ensure that a C300 Controller is properly installed in the same control cabinet as the
C300 Controller designated to become the redundant partner. Note do not connect
the Redundancy cable between the two controllers until instructed to do so.
Considerations
This procedure can be performed on-process. All illustrations used in the procedure are
for example purposes only.
To convert a non-redundant C300 Controller to a Redundant controller
Step Action Result
1
In the Project window, right-click on the
C300_NonRED Controller block icon.
Calls up shortcut menu.
2
Click Module Properties...
Calls up the C300 Block configuration
form.