Load components from Project
Component deletion considerations
R301.1 Experion C300 Controller User's Guide 145
11/06 Honeywell
Component deletion considerations
Control Strategy edits must be performed from the Project tab only.
Deleting blocks from the Project tab eliminates them from the Project version of the
database only. Only blocks that are not loaded can be deleted. Delete loaded blocks
from the Monitoring tab first before deleting them from the Project tab.
Deleting blocks from the Monitoring tab eliminates them from the controller, Server
and loaded version of the database. The blocks remain in the Project version of the
database.
ATTENTION
Changes to parameters in the controller can be made from the Monitoring
tab. See Changing Parameters while Monitoring section in the Control
Building Guide.
Load components from Project
Loading C300 Controller
Use the following general procedure to load a C300 Controller. The load procedure is
similar for all controller components.
Prerequisites
Control Builder is running
This procedure assumes that the C300 Controller is installed and capable of
communicating with the Server.
Considerations
Note that selecting a C300 Controller block for loading also selects the associated
CEEC300 block and IOLINK blocks.
All illustrations used in the procedure are for example purposes only.
To load a C300 Controller block and its associated blocks
Step Action Result
1
Click desired C300 block icon in Project
Selects and highlights the component.